Q-Trak Indoor Air Quality Meter
Easy-To-Use Air Quality Monitoring Instruments Providing Real-Time Measurements.
SKU
QTRAKIAQM
Providing a comfortable, safe and healthy indoor environment is an increasingly important concern. Good air quality increases concentration and productivity. It can also reduce lost days due to absence. TSI's Q-TRAK™ Indoor Air Quality Monitor 7575 provides quick, accurate information to assess key indoor air quality (IAQ) parameters.
On-screen prompts and step-by-step instructions guide the user through operation, instrument setup and field calibration. The Q-Trak IAQ Monitor 7575 also features an ergonomic, over moulded case design with probe holder and a keypad lockout to prevent tampering during unattended use. The Q-Trak IAQ Monitor 7575 is designed to work with a wide range of plug-in probes which expands measurement capability.
For more information on the Q-Trak Indoor Air Quality Meter, contact your local Air-Met office.
- Simultaneously displays CO2, CO, temperature and humidity measurements
- Calculates dew point, wet bulb and percent outside air
- Large graphic display
- Displays up to 5 measurements
- On-screen messages and instructions
- Supports 12 different languages
- One instrument with multiple plug-in probe options including VOC’s and air velocity
- Store up to 39 days of data collected at one-minute log intervals
- TRAKPRO™ data analysis software provided for data logging, analysis and documenting results
- Bluetooth communications for transferring data or remote polling
| CO2: | |
| Range: | 0 to 5000 ppm |
| Accuracy: | ±3% of reading or ±50 ppm, whichever is greater |
| Resolution: | 1 ppm |
| Sensor Type: | Non-Dispersive Infrared (NDIR) |
| Temperature: | |
| Range: | 32 to 140°F (0 to 60°C) |
| Accuracy: | ±1.0°F (±0.6°C) |
| Resolution: | 0.1°F (0.1°C) |
| Response time: | 30 seconds (90% of final value, air velocity at 400 ft/min[2 m/s]) |
| Type: | Thermistor |
| Relative Humidity: | |
| Range: | 5 to 95% RH |
| Accuracy: | ±3% RH (includes ±1% hysteresis.) |
| Resolution: | 0.1% RH |
| Response Time: | 20 seconds (for 63% of final value) |
| Sensor Type: | Thin-film capacitive |
| CO Sensor: | |
| Range: | 0 to 500 ppm |
| Accuracy: | ±3% of reading or 3 ppm whichever is greater [add ±0.5%/°C (0.28%/°F) away from calibration temperature] |
| Resolution: | 1 ppm |
| Response Time: | <60 seconds to 90% of final value. |
| Sensor Type: | Electro-chemical |
| Instrument Temperature Range: | |
| Operating (Electronics): | 40 to 113°F (5 to 45°C) |
| Storage: | -4 to 146°F (-20 to 60°C) |
| Instrument Operating Conditions: | |
| Altitude up to 4000 meters | |
| Relative humidity up to 80% RH, non-condensing | |
| Pollution degree 1 in accordance with IEC 664 | |
| Transient over voltage category II | |
| 14 Appendix A | |
| Data Storage Capabilities: | |
| Range: | Logs up to 56,035 data points with key (4) measured parameters enabled, 38.9 days at 1-minute log intervals |
| Logging Interval: | |
| Intervals: | 1 second to 1 hour (user selectable) |
| Time Constant: | |
| Intervals: | 1 sec, 5 sec, 10 sec, 20 sec, 30 sec, (user selectable) |
| External Meter Dimensions: | |
| 3.8 in. × 8.3 in. × 2.1 in. (9.7 cm × 21.1 cm × 5.3 cm) | |
| Meter Probe Dimensions: | |
| Probe length: 7.0 in. (17.8 cm) | |
| Probe diameter of tip: 0.75 in. (1.9 cm) | |
| Meter Weight: | |
| Weight with batteries: 0.8 lbs (0.36 kg) | |
| Power Requirements: | |
| Batteries: | Four AA-size alkaline or rechargeable |
| or | |
| AC adapter: | 6 VDC nominal, 300 mA [Q-TRAK monitor mates with 5.5 mm OD × 2.1 mm ID plug, center pin positive(+)] |
- IAQ investigations
- Industrial hygiene surveys
- Baseline trending and screening
- Building commissioning
- Tracking down emissions to their source (point source location)